access icon free Numerical analysis on the short-circuit withstanding performance of busbar system in LV switchgear

The short-circuit withstanding performance of busbar system is one of the most important safety indexes for low-voltage (LV) switchgear. The resonance characteristics, short-circuit displacement, and stress concentration of four typical busbar system arrangements are numerically analysed in this study. First, modal analysis is used to calculate the vibration modes and natural frequencies of the busbar systems. The influence of span length and phase-to-phase distance is discussed and thresholds for resonance prevention are given. Then, electromagnetic-structural coupled models are built to simulate the short-circuit mechanical response. The time-varying displacement and stress are obtained and the dynamic stability of typical arrangements is compared. The proposed results can provide theoretical reference for the dynamic stability design of busbar system in LV switchgear.

Inspec keywords: numerical analysis; modal analysis; short-circuit currents; switchgear

Other keywords: span length; phase-to-phase distance; stress concentration; busbar system arrangements; electromagnetic-structural coupled models; LV switchgear; time-varying displacement; dynamic stability; vibration modes; natural frequencies; short-circuit mechanical response; modal analysis; low-voltage switchgear; safety indexes; numerical analysis

Subjects: Other numerical methods; Switchgear

References

    1. 1)
      • 5. Yang, J., Liu, Y., Hu, D., et al: ‘Transient electromagnetic force analysis of GIS bus based on FEM’. 2016 Int. Conf. on Condition Monitoring and Diagnosis (CMD), Xi'an, 2016, pp. 554557.
    2. 2)
      • 1. Sun, L.: ‘Basic of electric power engineering’ (China Machine Press, USA., 2006).
    3. 3)
      • 6. Yang, J., Liu, Y., Hu, D., et al: ‘Transient vibration study of GIS bus based on FEM’. 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conf. (APPEEC), Xi'an, 2016, pp. 10921095.
    4. 4)
      • 8. Kadkhodaei, G., Sheshyekani, K., Hamzeh, M., et al: ‘Multiphysics analysis of busbars with various arrangements under short-circuit condition’, IET Electr. Syst. Transp., 2016, 6, (4), pp. 237245.
    5. 5)
      • 14. Dannenhoffer, J., Baron, J.: ‘Grid adaptation for the 2-D Euler equations’. 23rd Annual Scientific Meeting (ASM), New York, USA, 1985, pp. 111.
    6. 6)
      • 11. Ruan, J., Wu, Y., Li, P., et al: ‘Optimum methods of thermal-fluid numerical simulation for switchgear’, IEEE. Access., 2019, 7, pp. 3273532744.
    7. 7)
      • 9. Ling, D.: ‘Research on the short-circuit verifying of wires (in Chinese)’. MS thesis, Yangzhou University, 2001.
    8. 8)
      • 2. You, J., Wang, R., Liang, H., et al: ‘Research on the calculation methods of enclosed isolated phase bus-bar in short-circuit condition’. 2016 IEEE 62nd Holm Conf. on Electrical Contacts (Holm), Clearwater Beach, FL, 2016, pp. 111114.
    9. 9)
      • 12. Guan, X., Shu, N., Kang, B., et al: ‘Multiphysics analysis of plug-in connector under steady and short circuit conditions’, IEEE Trans. Compon. Packag. Manuf. Technol., 2015, 5, (3), pp. 320327.
    10. 10)
      • 3. Yusop, F.M., Jamil, M.K.M., Ishak, D., et al: ‘Investigation of electromagnetic force during short-circuit test in three-phase busbar system’. 2011 IEEE Colloquium on Humanities, Science and Engineering Research (CHUSER 2011), Penang2011, pp. 340344.
    11. 11)
      • 13. Wu, Y., Ruan, J., Gong, Y., et al: ‘Contact resistance model and thermal stability analysis of bolt structure’, IEEE Trans. Compon. Packag. Manuf. Technol., 2019, 9, (4), pp. 694701.
    12. 12)
      • 4. Yusop, F.M., Jamil, M.K.M., Ishak, D., et al: ‘Study on the electromagnetic force affected by short-circuit current in vertical and horizontal arrangement of busbar system’. Int. Conf. on Electrical, Control and Computer Engineering 2011 (InECCE), Pahang, 2011, pp. 196200.
    13. 13)
      • 10. Bian, C., Zhou, Y., Guan, W., et al: ‘Study on the closing state of high voltage disconnectors based on the modal analysis’. 2017 20th Int. Conf. on Electrical Machines and Systems (ICEMS), Sydney, NSW, 2017, pp. 15.
    14. 14)
      • 7. Guan, X., Shu, N., Jin, X., et al: ‘Temperature and electromagnetic force analysis of GIB plug-in connector with different contact status under short circuit fault’. 2016 IEEE Conf. on Electromagnetic Field Computation (CEFC), Miami, FL, 2016, pp. 11.
http://iet.metastore.ingenta.com/content/journals/10.1049/iet-smt.2019.0169
Loading

Related content

content/journals/10.1049/iet-smt.2019.0169
pub_keyword,iet_inspecKeyword,pub_concept
6
6
Loading