access icon openaccess Identification of slot discharges in rotating machine insulation system using variable frequency PD measurement

Slot discharge studies are very important from the insulation diagnosis perspective. Further in practice, testing of rotating machines with power frequency requires sources which are quite bulky and costly. Instead if the diagnosis is carried out at lower frequencies (<50 Hz), the size and cost of the test source can be reduced significantly. Therefore, it is important to know whether the study at low frequencies can be considered equivalent to study at power frequency. Hence, in this study, a slot discharge phenomenon occurring in a rotating machine insulation system was investigated experimentally at different frequencies (50, 10, 1 and 0.1 Hz). Slot discharges are known to have a distinct phase resolved partial discharge pattern for power frequency (50/60 Hz) excitation. These distinct patterns are useful in identifying the presence of slot discharge activity in rotating machines. Slot discharges were created on a 6.6 kV mica-epoxy stator coil and the slot discharge characteristics measured at different frequencies are compared. Slot discharge measurements were repeated by varying the air gap between the insulation surface and grounded steel plate. The changes in slot discharge characteristics due to the increase in air gap were found similar at all frequencies. The comparison suggests that the identification of slot discharge is also possible from the partial discharge (PD) measurement at low frequencies.

Inspec keywords: electric machines; frequency measurement; high-frequency discharges; epoxy insulation; coils; partial discharge measurement; air gaps; stators

Other keywords: insulation surface; slot discharge phenomenon; insulation diagnosis perspective; air gap; power frequency; rotating machine insulation system; phase resolved partial discharge pattern; variable frequency PD measurement; slot discharge characteristics; mica-epoxy stator coil; slot discharge measurements; grounded steel plate; rotating machine testing; slot discharge activity identification

Subjects: d.c. machines; a.c. machines; Charge measurement; Frequency measurement; Inductors and transformers; Dielectric breakdown and discharges; Organic insulation

References

    1. 1)
      • 18. Forssen, C., Edin, H.: ‘Partial discharges in a cavity at variable applied frequency part 1: measurements’, IEEE Trans. Instrum. Meas., 2008, 15, (6), pp. 16011609.
    2. 2)
      • 15. Miller, R., Black, I.A.: ‘Partial discharge measurements over the frequency range 0.1 Hz to 50 Hz’, IEEE Trans. Electr. Insul., 1977, 12, pp. 224233.
    3. 3)
      • 4. Stone, G.C., Maughan, C.V., Nelson, D., et al: ‘Impact of slot discharges and vibration sparking on stator winding life in large generators’, IEEE Electr. Insul. Mag., 2008, 24, (5), pp. 1421.
    4. 4)
      • 19. Bodega, R., Morshuis, P.H.F., Lazzaroni, M., et al: ‘PD recurrence in cavities at different energizing methods’, IEEE Trans. Instrum. Meas., 2004, 53, (2), pp. 251258.
    5. 5)
      • 9. Farahani, M., Borsi, H., Gockenbach, E., et al: ‘Partial discharge and dissipation factor behavior of model insulating systems for high voltage rotating machines under different stresses’, IEEE Electr. Insul. Mag., 2005, 21, (5), pp. 518.
    6. 6)
      • 20. Nguyen, H.V.P., Phung, B.T., Blackburn, T.: ‘Effects of ambient conditions on partial discharges at very low frequency (VLF) sinusoidal voltage excitation’. Proc. Int. Conf. on Electrical Insulation Conf. (EIC), Seattle, WA, USA, 2015, pp. 266269.
    7. 7)
      • 22. IEC 60270: ‘High-voltage test techniques – partial discharge measurements’, 2012.
    8. 8)
      • 2. Li, S., Li, J.: ‘Condition monitoring and diagnosis of power equipment: review and prospective’, High Volt., 2017, 2, (2), pp. 8291.
    9. 9)
      • 25. Al-Arainy, A.A., Malik, N.H., Al-Bahloul, M.K.: ‘Statistical variation of AC corona pulse amplitudes in point-to-plane air gaps’, IEEE Trans. Electr. Insul., 1989, 24, (4), pp. 681687.
    10. 10)
      • 12. Belec, M., Hudon, C., Guddemi, C.: ‘Laboratory study of slot discharge characteristic PRPD patterns’. Proc. Electrical Insulation Conf. and Electrical Manufacturing and Coil Winding Conf., Cincinnati, OH, USA, 2001, pp. 547550.
    11. 11)
      • 21. Nyamupangedengu, C., Jandrell, I.R.: ‘Partial discharge spectral response to variations in the supply voltage frequency’, IEEE Trans. Dielectr. Electr. Insul., 2012, 19, (2), pp. 521532.
    12. 12)
      • 3. IEEE 1434-2014: ‘Guide for the measurement of partial discharges in AC electric machinery’, 2014.
    13. 13)
      • 16. Miller, R., Black, I.A.: ‘Partial discharge energy measurements on electrical machine insulation when energized at frequencies between 0.1 Hz and power frequency’, IEEE Trans. Electr. Insul., 1979, 14, pp. 127135.
    14. 14)
      • 13. Joyo, T., Okuda, T., Kadota, N., et al: ‘Phase resolved partial discharge patterns for various damage of winding insulation detected with different measuring devices’. Proc. Int. Conf. on Electrical Insulation Conf. (EIC), Baltimore, MD, USA, 2017, pp. 344347.
    15. 15)
      • 8. Levesque, M., David, E., Hudon, C., et al: ‘Effect of surface conditions on slot partial discharge activity’, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, (5), pp. 14281440.
    16. 16)
      • 7. Hudon, C., Belec, M., Levesque, M.: ‘Study of slot partial discharges in air-cooled generators’, IEEE Trans. Dielectr. Electr. Insul., 2008, 15, (6), pp. 16751690.
    17. 17)
      • 11. Song, J., Li, C., Lin, L., et al: ‘Slot discharge pattern of 10 kV induction motor stator coils under condition of insulation degradation’, IEEE Trans. Dielectr. Electr. Insul., 2013, 20, (6), pp. 20912098.
    18. 18)
      • 1. Stone, G.C.: ‘Condition monitoring and diagnostics of motor and stator windings – a review’, IEEE Trans. Dielectr. Electr. Insul., 2013, 20, (6), pp. 20732080.
    19. 19)
      • 14. IEEE 433-2009: ‘IEEE recommended practice for insulation testing of AC electric machinery with high voltage at very low frequency’, 2009.
    20. 20)
      • 17. Cavallini, A., Montanari, G.C.: ‘Effect of supply voltage frequency on testing of insulation system’, IEEE Trans. Dielectr. Electr. Insul., 2006, 13, (5), pp. 111121.
    21. 21)
      • 6. Greg Stone, C., Culbert, I., Edward Boulter, A., et al: ‘Rotating machine insulation systems’, in El-Hawary, M.E. (Ed.): ‘Electrical insulation for rotating machines: design, evaluation, aging, testing, and repair’, vol. 1 (Wiley-IEEE Press, Piscataway, NJ, 2004), pp. 140.
    22. 22)
      • 10. Levesque, M., David, E., Hudon, C., et al: ‘Contribution of humidity to the evolution of slot partial discharges’, IEEE Trans. Dielectr. Electr. Insul., 2012, 19, (1), pp. 6175.
    23. 23)
      • 24. Abdel Salam, M., Weiss, P.: ‘Discharges in air from point electrodes in the presence of dielectric plates’, IEEE Trans. Electr. Insul., 1992, 27, (2), pp. 320333.
    24. 24)
      • 5. Jackson, R.J., Wilson, A.: ‘Slot discharge activity in air-cooled motors and generators’, IEE Proc. B, Electr. Power Appl., 1982, 129, pp. 159167.
    25. 25)
      • 23. Florkowska, B., Wlodek, R.: ‘Pulse height analysis of partial discharges in air’, IEEE Trans. Dielectr. Electr. Insul., 1993, 28, (6), pp. 932940.
http://iet.metastore.ingenta.com/content/journals/10.1049/hve.2017.0176
Loading

Related content

content/journals/10.1049/hve.2017.0176
pub_keyword,iet_inspecKeyword,pub_concept
6
6
Loading