Composite porcelain insulators are a new type of insulator. At present, the number of various types of composite porcelain insulators in operation at various voltage levels in China Power Grid has reached 3 million pieces, and its operating status has not been studied at present. This article summarizes the problems found in the anti-pollution treatment of UHV lines, and introduces the application history and current status of composite porcelain insulators. Sampling and testing of 42 pieces of 3 different types of DC composite porcelain insulators running for 4 years, it was found that with the exception of 21.4% of the test samples, the hydrophobicity was reduced to HC4 (including HC3-HC4), and other sampling indicators met the requirements of the standard. It was suggested that the storage, handling, installation and operation maintenance management of composite porcelain insulators should be strengthened.
Inspec keywords: insulator contamination; porcelain insulators; maintenance engineering; insulator testing; ceramic insulators; power grids; power transmission reliability; power transmission lines
Subjects: Reliability; Power line supports, insulators and connectors; Maintenance and reliability