Your recommendation has been sent to your librarian.
The current fault restart/reclose method for flexible direct current (DC) grid is to see whether the DC voltage can be established when the converter is unlocked again. This method will cause secondary damage to the grid once restarting with the permanent fault. Due to the problem of fault restart/reclose of modular multilevel converter (MMC)-based DC grid, A restart/reclose method based on pulse voltage injection is studied in this paper. The pulse voltage can be injected by the full bridge (FB) MMC or the transfer branch of DC breaker. If the fault disappears, the pulse voltage can lead to full voltage, otherwise, the voltage is still low. builds the pulse voltage injection control strategy for FB-MMC and the DC breaker with transfer branch is built in PSCAD simulation system. The proposed method can also judge the fault type by the highest voltage raised by the pulse voltage. The simulation verifies the effectiveness of the proposed restart/reclose method.
Inspec keywords: HVDC power transmission; circuit breakers; HVDC power convertors; power transmission control; power grids; voltage control; power transmission faults; bridge circuits; voltage-source convertors; power system CAD
Subjects: Voltage control; d.c. transmission; AC-DC power convertors (rectifiers); Switchgear; Power engineering computing; DC-AC power convertors (invertors); Power system control; Control of electric power systems; Power electronics, supply and supervisory circuits