Short Circuit Currents
Buy book PDF
- $124.00
The calculation of short circuit currents is a central task for Power System engineers, they are essential parameters for the design of electrical equipment and installations, the operation of power systems and the analysis of outages and faults.
Inspec keywords: earthing; short-circuit currents; fault currents
Other keywords: short-circuit current calculation; AC three-phase HV-system; neutral earthing influence; impedance calculation; double earth-fault current; low-voltage system; electrical equipment; DC auxiliary installation
Subjects: Power system protection
- Book DOI: 10.1049/PBPO051E
- Chapter DOI: 10.1049/PBPO051E
- ISBN : 9780863415142
- e-ISBN: 9781849190480
- Page count: 336
- Format: PDF
-
Front Matter
- + Show Description
-
Hide details
- + Show Description
-
-
1 Introduction
- + Show Description
-
Hide details
-
p.
1
–10
(10)
This book deals with the calculation of short-circuit currents in two- and three-phase a.c. systems as well as in d.c. systems, installed as auxiliary installations in power plants and substations. It is not the objective of this book to repeat definitions and rules of norms and standards, but to explain the procedure for calculating short-circuit currents and their effects on installations and equipment. In some cases repetition of equations, tables and diagrams from norms and standards however are deemed necessary for easy understanding. It should be emphasised in this respect that the presentation within this book is mainly concentrated on installations and equipment in high voltage systems, i.e., voltage levels up to 500 kV. Special considerations have to be taken in the case of long transmission lines and in power systems with nominal voltages above 500 kV. The calculation of short-circuit currents and of their effects are based on the procedures and rules defined in the IEC documents 61660, 60909, 60865 and 60781.
- + Show Description
-
-
2 Theoretical background
- + Show Description
-
Hide details
-
p.
11
–44
(34)
A detailed deduction of the mathematical procedure is not given within the context of this book, but only the final equations are quoted. In general, equipment in power systems is represented by equivalent circuits, which are designed for the individual tasks of power system analysis. For the calculation of no-load current and the no-load reactive power of a transformer, the no-load equivalent circuit is sufficient. Regarding the calculation of short-circuits, voltage drops and load characteristic a different equivalent circuit is required. The individual components of the equivalent circuits are resistance, inductive and capaci tive reactance (reactor and capacitor), voltage source and ideal transformer. Voltage and currents of the individual components and of the equivalent circuit are linked by Ohm's law.
- + Show Description
-
-
3 Calculation of impedance of electrical equipment
- + Show Description
-
Hide details
-
p.
45
–66
(22)
In general, equipment in power systems are represented by equivalent circuits, which are designed for the individual tasks of power system analysis, e.g., for the calculation of no-load current and the no-load reactive power of a transformer, the no-load equivalent circuit is sufficient. Regarding the calculation of short-circuits, voltage drops and load characteristic a different equivalent circuit is required. The individual components of the equivalent circuits are resistance, inductive and capacitive reactance (reactor and capacitor), voltage source and ideal transformer. Voltage and currents of the individual components and of the equivalent circuit are interlaced by Ohm's law, which is valid for the three-phase system (RYB-system) as well as for the system of symmetrical components (012-system). A detailed deduction of the mathematical methods and equations is not given within the context of this section of the book, but only the final equations are quoted.
- + Show Description
-
-
4 Calculation of short-circuit current in a.c. three-phase HV-systems
- + Show Description
-
Hide details
-
p.
67
–96
(30)
In this chapter, an outline of different types of short-circuits in three-phase a.c. systems is provided such as three-phase short-circuit,double-phase short-circuit without earth/ground connection, double-phase short-circuit with earth/ground connection and line-to-earth (line-to-ground) short-circuit. The method for calculating short-circuit current in a.c. three-phase high-voltage system is also provided.
- + Show Description
-
-
5 Influence of neutral earthing on single-phase short-circuit currents
- + Show Description
-
Hide details
-
p.
97
–130
(34)
The theoretical approach to calculate short-circuit (s.-c.) currents with symmetrical components in general and especially in the case of single-phase short-circuit was explained in detail in Chapter 2. Current and voltages in case of short-circuits with earth connection (e.g., single-phase short-circuits) depend on the positive and zero sequence impedances Z1 and Z0.
- + Show Description
-
-
6 Calculation of short-circuit currents in low-voltage systems
- + Show Description
-
Hide details
-
p.
131
–138
(8)
IEC 60781 presents an application guide for the calculation of short-circuit currents in low-voltage radial systems. The short-circuits are treated as far-from-generator short-circuits. This assumption is valid in the future as well, even with an increasing number of distributed generation units in low-voltage systems.
- + Show Description
-
-
7 Double earth-fault and short-circuit currents through earth
- + Show Description
-
Hide details
-
p.
139
–150
(12)
Chapter 7 discusses the double earth fault and shot circuit current through earth. Branch short-circuit currents can flow through earth in the case of unbalanced short circuits with earth connection, i.e., line-to-earth (single-phase) short-circuit and double-phase short-circuit with earth connection. Single-phase short-circuits are the dominating fault type in power systems with earthed neutrals and are leading to the maximal branch short-circuit currents flowing through earth.
- + Show Description
-
-
8 Factors for the calculation of short-circuit currents
- + Show Description
-
Hide details
-
p.
151
–164
(14)
Several factors for the calculation of short-circuit (s.-c.) currents have been introduced in previous sections, the origin of which will be explained within this section. · Voltage factor cmax and cmin for different voltage levels as per Table 4.1. · Correction factor using the %/MVA or the p.u.-system as mentioned in Chapter 2. · Impedance correction factors for synchronous machines, power station units and transformers as per Tables 3.2, 3.3, 3.5 and 3.6. · Factors for the calculation of different parameters of the short-circuit current based on the initial short-circuit current as per Chapter 4. The factors are necessary as the method of the equivalent voltage source at the short-circuit location is used for the calculation of short-circuit currents which is based on some simplifications such as neglecting the load current prior to fault, assuming the tap-changer of transformers in middle-position, calculating the impedance of equipment based on the name-plate data or on data for rated operating conditions and neglecting voltage control gear for generators and transformers. The main task of short-circuit analysis is to determine the maximal short-circuit current which is one of the main criteria for the rating of equipment in electrical power systems. It is obvious that the parameters of the short-circuit current as calculated with the equivalent voltage source at the short-circuit location will differ from those currents, which may be measured during short-circuit tests or may be calculated with transient network analysing programmes. In order to obtain results on the safe side without uneconomic safety margin the correction factors will be applied. Detailed deductions of the various correction factors are given in IEC 60909-1:1991-10.
- + Show Description
-
-
9 Calculation of short-circuit currents in d.c auxiliary installations
- + Show Description
-
Hide details
-
p.
165
–194
(30)
The calculation of short-circuit currents in d.c. auxiliary installations, e.g., in power plants and substations is dealt with in IEC 61660-1. Contrary to the approach for the calculation of short-circuit currents in a.c. three-phase systems, the determination of the exact time course of the short-circuit current is needed besides the calculation of defined parameters.
- + Show Description
-
-
10 Effects of short-circuit currents
- + Show Description
-
Hide details
-
p.
195
–224
(30)
Calculation methods for the thermal and electromagnetic effects of short-circuit currents are dealt with IEC 61660-2, which is applicable to short-circuit currents in d.c. auxiliary installations in power plants and substations and IEC 60865-1, related to three-phase a.c. systems.
- + Show Description
-
-
11 Limitation of short-circuit currents
- + Show Description
-
Hide details
-
p.
225
–244
(20)
The expansion of electrical power systems by new power stations and new lines (overhead transmission lines and cable circuits) results in an increase of short-circuit currents due to an increase in sources feeding the short-circuit and due to a reduction of system impedance. The improvement of existing installations and the replacement of equipment are necessary, in case the permissible short-circuit current will be exceeded. Measures to limit the short-circuit currents can also be realised which might be more economic than the replacement of equipment and installations. Different measures have to be taken into account such as measures affecting the whole system (higher voltage level), measures concerning installations and substations (separate operation of busbars) and measures related to equipment (Ip-limiter).
- + Show Description
-
-
12 Special problems related to short-circuit currents
- + Show Description
-
Hide details
-
p.
245
–266
(22)
Interference between overhead lines, communication circuits and pipelines is caused by asymmetrical currents, which may be due to short-circuits, asymmetrical operation or asymmetrical design of equipment, especially asymmetrical outline of overhead line towers with respect to pipelines and communication circuits. This interference is based on inductive, ohmic and capacitive coupling between the short-circuit path (e.g., overhead line) and the circuit affected by interference (e.g., pipeline). Normal operating currents, respectively voltages, cause magnetic as well as electric fields which are asymmetrical in the vicinity of overhead lines which may cause interference problems in the long-time range.
- + Show Description
-
-
13 Data of equipment
- + Show Description
-
Hide details
-
p.
267
–286
(20)
A summary of relevant data of equipment is given in IEC 60909-2:1992. The data is based on a survey carried out by IEC TC 73.
- + Show Description
-
-
Back Matter
- + Show Description
-
Hide details
-
p.
287
(1)
- + Show Description
-

